u H3: Multi-Function Analog InputsNo.(Addr.Hex) Name Description Values PageH3-01(410) Terminal A1 Signal LevelSelection 0: 0 to 10 V1: -10 to 10 V Default: 0Range: 0, 1 107H3-02(434) Terminal A1 FunctionSelection Sets the function of terminal A1. Default: 0Range: 0 to 31 107H3-03(411) Terminal A1 Gain SettingSets the level of the input value selected in H3-02 when 10 V is input atterminal A1. Default: 100.0%Min.: -999.9Max.: 999.9 107H3-04(412) Terminal A1 Bias SettingSets the level of the input value selected in H3-02 when 0 V is input at terminalA1. Default: 0.0%Min.: -999.9Max.: 999.9 107H3-05(413) Terminal A3 Signal LevelSelection 0: 0 to 10 V1: -10 to 10 V Default: 0Range: 0, 1 108H3-06(414) Terminal A3 FunctionSelection Sets the function of terminal A3. Default: 2Range: 0 to 31 108H3-07(415) Terminal A3 Gain SettingSets the level of the input value selected in H3-06 when 10 V is input atterminal A3. Default: 100.0%Min.: -999.9Max.: 999.9 108H3-08(416) Terminal A3 Bias SettingSets the level of the input value selected in H3-06 when 0 V is input at terminalA3. Default: 0.0%Min.: -999.9Max.: 999.9 108H3-09(417) Terminal A2 Signal LevelSelection0: 0 to 10 V1: -10 to 10 V2: 4 to 20 mA3: 0 to 20 mANote: Use DIP switch S1 to set input terminal A2 for a current or a voltageinput signal.Default: 2Range: 0 to 3 109H3-10(418) Terminal A2 FunctionSelection Sets the function of terminal A2. Default: 0Range: 0 to 31 109H3-11(419) Terminal A2 Gain SettingSets the level of the input value selected in H3-10 when 10 V (20 mA) is inputat terminal A2. Default: 100.0%Min.: -999.9Max.: 999.9 109H3-12(41A) Terminal A2 Bias SettingSets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) isinput at terminal A2. Default: 0.0%Min.: -999.9Max.: 999.9 109H3-13(41B) Analog Input Filter TimeConstantSets a primary delay filter time constant for terminals A1, A2, and A3. Usedfor noise filtering. Default: 0.03 sMin.: 0.00Max.: 2.00 –H3-14(41C) Analog Input TerminalEnable SelectionDetermines which analog input terminals will be enabled when a digital inputprogrammed for “Analog input enable” (H1-oo = C) is activated.1: Terminal A1 only2: Terminal A2 only3: Terminals A1 and A2 only4: Terminal A3 only5: Terminals A1 and A36: Terminals A2 and A37: All terminals enabledDefault: 7Range: 1 to 7 –H3-16(2F0) Terminal A1 Offset Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0Min.: -500Max.: 500 –H3-17(2F1) Terminal A2 Offset Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0Min.: -500Max.: 500 –H3-18(2F2) Terminal A3 Offset Adds an offset when the analog signal to terminal A3 is at 0 V. Default: 0Min.: -500Max.: 500 –B.7 H Parameters: Multi-Function Terminals210 YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide