u E4: Motor 2 ParametersThese parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).No.(Addr.Hex) Name Description Values PageE4-01(321) Motor 2 Rated CurrentSets the full load current for motor 2. Automatically set during Auto-Tuning. Default: <1>Min.: 10% of driverated currentMax.: 200% ofdrive rated current<2>–E4-02(322) Motor 2 Rated SlipSets the rated slip for motor 2. Automatically set during Auto-Tuning. Default: <1>Min.: 0.00 HzMax.: 20.00 Hz <2>–E4-03(323) Motor 2 Rated No-LoadCurrentSets the no-load current for motor 2. Automatically set during Auto-Tuning. Default: <1>Min.: 0 AMax.: E4-01 <2>–E4-04(324) Motor 2 Motor Poles Sets the number of poles of motor 2. Automatically set during Auto-Tuning. Default: 4Min.: 2Max.: 48 –E4-05(325) Motor 2 Line-to-LineResistanceSets the phase-to-phase resistance for motor 2. Automatically set duringAuto-Tuning.Note: The units are expressed in mΩ in models CIMR-Ao4A0930 and4A1200.Default: <1>Min.: 0.000 ΩMax.: 65.000 Ω–E4-06(326) Motor 2 Leakage InductanceSets the voltage drop for motor 2 due to motor leakage inductance as apercentage of rated voltage. Automatically set during Auto-Tuning. Default: <1>Min: 0.0%Max: 40.0%–E4-07(343) Motor 2 Motor Iron-CoreSaturation Coefficient 1 Set to the motor iron saturation coefficient at 50% of magnetic flux for motor2. Automatically set during Auto-Tuning.Default: 0.50Min.: 0.00Max.: 0.50 –E4-08(344) Motor 2 Motor Iron-CoreSaturation Coefficient 2Set to the motor iron saturation coefficient at 75% of magnetic flux for motor2. This value is automatically set during Auto-Tuning. Default: 0.75Min.: E4-07Max.: 0.75 –E4-09(33F) Motor 2 Mechanical Loss Sets the motor mechanical loss for motor 2 as a percentage of motor ratedpower (kW). Default: 0.0%Min.: 0.0Max.: 10.0 –E4-10(340) Motor 2 Iron LossSets the motor iron loss. Default: <1>Min.: 0 WMax.: 65535 W–E4-11(327) Motor 2 Rated PowerSets the motor rated capacity in kW. Automatically set during Auto-Tuning. Default: <1>Min.: 0.00 kWMax.: 650.00 kW–<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has twodecimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) ifthe maximum applicable motor capacity is higher than 11 kW.B.5 E: Motor Parameters196 YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide