Table 119:GUPPDUP Group settings (advanced)Name Values (Range) Unit Step Default Descriptionk 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for powermeasurement, U and ITable 120:GUPPDUP Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValuegroupsMode L1, L2, L3AronePos SeqL1L2L2L3L3L1L1L2L3- - Pos Seq Mode of measurement for current andvoltage8.8.3.5 Monitored dataTable 121:GUPPDUP Monitored dataName Type Values (Range) Unit DescriptionP REAL - MW Active PowerPPERCENT REAL - % Active power in % ofcalculated power basevalueQ REAL - MVAr Reactive powerQPERCENT REAL - % Reactive power in % ofcalculated power basevalue8.8.4 Operation principleA simplified scheme showing the principle of the power protection function is shownin figure 88. The function has two stages with individual settings.Section 8 1MRK 504 135-UEN ACurrent protection194Technical manual