Table 467:RS485103 Non group settings (basic)Name Values (Range) Unit Step Default DescriptionSlaveAddress 1 - 255 - 1 1 Slave addressBaudRate 9600 Bd19200 Bd- - 9600 Bd Baudrate on serial lineCycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurmentsMasterTimeDomain UTCLocalLocal with DST- - UTC Master time domainTimeSyncMode IEDTimeLinMastTimeIEDTimeSkew- - IEDTime Time synchronization modeEvalTimeAccuracy Off5ms10ms20ms40ms- - 5ms Evaluate time accuracy for invalid timeEventRepMode SeqOfEventHiPriSpont- - SeqOfEvent Event reporting mode16.12 IEC 61850-8-1 redundant station bus communicationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSystem component for parallelredundancy protocolPRPSTATUS - -16.12.1 FunctionalityRedundant station bus communication according to IEC 62439-3 Edition 2 isavailable as option in the Customized 650 Ver 1.3 series IEDs, and the selection ismade at ordering. Redundant station bus communication according to IEC 62439-3Edition 2 uses both ports LAN1A and LAN1B on the COM03 module.Select COM03 for redundant station bus according to IEC 62439-3Edition 2 protocol, at the time of ordering.IEC 62439-3 Edition 2 is NOT compatible with IEC 62439-3 Edition1.16.12.2 Principle of operationThe redundant station bus communication is configured using the local HMI, MainMenu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB.The settings are also visible in PST in PCM600.1MRK 504 135-UEN A Section 16Station communication551Technical manual