Name Values (Range) Unit Step Default DescriptionQLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)UGenZeroDb 1 - 100 %UB 1 5 Zero point clamping in % of UbasePFDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sPFZeroDb 0 - 100000 m% 1 500 Zero point clampingIGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of IbasePFHiHiLim -1.000 - 1.000 - 0.001 1.000 High High limit (physical value)PFHiLim -1.000 - 1.000 - 0.001 0.800 High limit (physical value)PFLowLim -1.000 - 1.000 - 0.001 -0.800 Low limit (physical value)PFLowLowLim -1.000 - 1.000 - 0.001 -1.000 Low Low limit (physical value)PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)UDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sUZeroDb 0 - 100000 m% 1 500 Zero point clampingUHiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBaseUHiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBaseULowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBaseULowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBaseULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)IDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sIZeroDb 0 - 100000 m% 1 500 Zero point clampingIHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBaseIHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBaseILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBaseILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBaseILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)FrDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sFrZeroDb 0 - 100000 m% 1 500 Zero point clampingFrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at 5%of UrUAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at30% of UrTable continues on next pageSection 14 1MRK 504 135-UEN AMonitoring414Technical manual