Name Values (Range) Unit Step Default DescriptionURepTyp CyclicDead bandInt deadband- - Dead band Reporting typeULimHys 0.000 - 100.000 V 0.001 5.000 Hysteresis value in % of range and iscommon for all limitsUAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sTable 355:VNMMXU Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionUZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of rangeUHiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)UHiLim 0 - 2000000 V 1 86000 High limit (physical value)ULowLim 0 - 2000000 V 1 71000 Low limit (physical value)ULowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)UMin 0 - 2000000 V 1 0 Minimum value14.1.7.5 Monitored dataTable 356:VNMMXU Monitored dataName Type Values (Range) Unit DescriptionUL1 REAL - kV UL1 Amplitude,magnitude of reportedvalueUL1ANGL REAL - deg UL1 Angle, magnitude ofreported valueUL2 REAL - kV UL2 Amplitude,magnitude of reportedvalueUL2ANGL REAL - deg UL2 Angle, magnitude ofreported valueUL3 REAL - kV UL3 Amplitude,magnitude of reportedvalueUL3ANGL REAL - deg UL3 Angle, magnitude ofreported value14.1.8 Operation principle14.1.8.1 Measurement supervisionThe protection, control, and monitoring IEDs have functionality to measure andfurther process information for currents and voltages obtained from the pre-1MRK 504 135-UEN A Section 14Monitoring427Technical manual