Table 220:ABC_LINE Output signalsName Type DescriptionQA1CLREL BOOLEAN Closing of QA1 is allowedQA1CLITL BOOLEAN Closing of QA1 is forbiddenQB9REL BOOLEAN Switching of QB9 is allowedQB9ITL BOOLEAN Switching of QB9 is forbiddenQB1REL BOOLEAN Switching of QB1 is allowedQB1ITL BOOLEAN Switching of QB1 is forbiddenQB2REL BOOLEAN Switching of QB2 is allowedQB2ITL BOOLEAN Switching of QB2 is forbiddenQB7REL BOOLEAN Switching of QB7 is allowedQB7ITL BOOLEAN Switching of QB7 is forbiddenQC1REL BOOLEAN Switching of QC1 is allowedQC1ITL BOOLEAN Switching of QC1 is forbiddenQC2REL BOOLEAN Switching of QC2 is allowedQC2ITL BOOLEAN Switching of QC2 is forbiddenQC9REL BOOLEAN Switching of QC9 is allowedQC9ITL BOOLEAN Switching of QC9 is forbiddenQB1OPTR BOOLEAN QB1 is in open positionQB1CLTR BOOLEAN QB1 is in closed positionQB2OPTR BOOLEAN QB2 is in open positionQB2CLTR BOOLEAN QB2 is in closed positionQB7OPTR BOOLEAN QB7 is in open positionQB7CLTR BOOLEAN QB7 is in closed positionQB12OPTR BOOLEAN QB1 or QB2 or both are in open positionQB12CLTR BOOLEAN QB1 and QB2 are not in open positionVPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open orclosed)12.2.7.6 SettingsThe function does not have any settings available in Local HMI or Protection andControl IED Manager (PCM600).12.2.8 Interlocking for transformer bay AB_TRAFO1MRK 504 135-UEN A Section 12Control321Technical manual