Table 432:PCGGIO Output signalsName Type DescriptionINVALID BOOLEAN The pulse counter value is invalidRESTART BOOLEAN The reported value does not comprise a completeintegration cycleBLOCKED BOOLEAN The pulse counter function is blockedNEW_VAL BOOLEAN A new pulse counter value is generatedSCAL_VAL REAL Scaled value with time and status information15.1.5 SettingsTable 433:PCGGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnEventMask NoEventsReportEvents- - NoEvents Report mask for analog events from pulsecounterCountCriteria OffRisingEdgeFalling edgeOnChange- - RisingEdge Pulse counter criteriaScale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to unitper counted valueQuantity CountActivePowerApparentPowerReactivePowerActiveEnergyApparentEnergyReactiveEnergy- - Count Measured quantity for SCAL_VAL outputtReporting 1 - 3600 s 1 60 Cycle time for reporting of counter value15.1.6 Monitored dataTable 434:PCGGIO Monitored dataName Type Values (Range) Unit DescriptionCNT_VAL INTEGER - - Actual pulse countervalueSCAL_VAL REAL - - Scaled value with timeand status information15.1.7 Operation principleThe registration of pulses is done according to setting of CountCriteria parameter onone of the 9 binary input channels located on the BIO module. Pulse counter values aresent to the station HMI with predefined cyclicity without reset.Section 15 1MRK 504 135-UEN AMetering526Technical manual