12.1.5.5 SettingsTable 189:QCBAY Non group settings (basic)Name Values (Range) Unit Step Default DescriptionAllPSTOValid PriorityNo priority- - Priority Priority of originators12.1.6 Local remote LOCREM12.1.6.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote LOCREM - -12.1.6.2 FunctionalityThe signals from the local HMI or from an external local/remote switch are applied viathe function blocks LOCREM and LOCREMCTRL to the Bay control QCBAYfunction block. A parameter in function block LOCREM is set to choose if the switchsignals are coming from the local HMI or from an external hardware switch connectedvia binary inputs.12.1.6.3 Function blockLOCREMCTRLOFFLOCCTRLREMCTRLLHMICTRLOFFLOCALREMOTEVALIDIEC09000076_1_en.vsdIEC09000076 V1 ENFigure 119: LOCREM function block12.1.6.4 SignalsTable 190:LOCREM Input signalsName Type Default DescriptionCTRLOFF BOOLEAN 0 Disable controlLOCCTRL BOOLEAN 0 Local in controlREMCTRL BOOLEAN 0 Remote in controlLHMICTRL INTEGER 0 LHMI control1MRK 504 135-UEN A Section 12Control263Technical manual