( )Old CalculatedS k S 1 k S= × + - ×EQUATION1959 V1 EN (Equation 66)WhereS is a new measured value to be used for the protection functionSold is the measured value given from the function in previous execution cycleSCalculated is the new calculated value in the present execution cyclekTDis settable parameter by the end user which influence the filter propertiesDefault value for parameter k is 0.00. With this value the new calculated value isimmediately given out without any filtering (that is without any additional delay).When k is set to value bigger than 0, the filtering is enabled. A typical value for k=0.92in case of slow operating functions.8.8.5 Technical dataTable 123:GOPPDOP, GUPPDUP technical dataFunction Range or value AccuracyPower level (0.0–500.0)% ofSBase ± 1.0% of Sr at S < Sr± 1.0% of S at S > Sr(1.0-2.0)% ofSBase < ± 50% of set value(2.0-10)% ofSBase < ± 20% of set valueCharacteristic angle (-180.0–180.0) degrees 2 degreesTimers (0.010 - 6000.000) s ± 0.5% ± 25 ms8.9 Negative sequence based overcurrent functionDNSPTOC8.9.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberNegative sequence based overcurrentfunctionDNSPTOC3I2>IEC09000132 V2 EN461MRK 504 135-UEN A Section 8Current protection197Technical manual