Name Type DescriptionP11 BOOLEAN Selector switch position 11P12 BOOLEAN Selector switch position 12P13 BOOLEAN Selector switch position 13P14 BOOLEAN Selector switch position 14P15 BOOLEAN Selector switch position 15P16 BOOLEAN Selector switch position 16P17 BOOLEAN Selector switch position 17P18 BOOLEAN Selector switch position 18P19 BOOLEAN Selector switch position 19P20 BOOLEAN Selector switch position 20P21 BOOLEAN Selector switch position 21P22 BOOLEAN Selector switch position 22P23 BOOLEAN Selector switch position 23P24 BOOLEAN Selector switch position 24P25 BOOLEAN Selector switch position 25P26 BOOLEAN Selector switch position 26P27 BOOLEAN Selector switch position 27P28 BOOLEAN Selector switch position 28P29 BOOLEAN Selector switch position 29P30 BOOLEAN Selector switch position 30P31 BOOLEAN Selector switch position 31P32 BOOLEAN Selector switch position 32SWPOSN INTEGER Switch position as integer value12.4.5 SettingsTable 247:SLGGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnNrPos 2 - 32 - 1 32 Number of positions in the switchOutType PulsedSteady- - Steady Output type, steady or pulsetPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse durationtDelay 0.000 - 60000.000 s 0.010 0.000 Output time delayStopAtExtremes DisabledEnabled- - Disabled Stop when min or max position is reachedSection 12 1MRK 504 135-UEN AControl354Technical manual