ANDBLOCKTRINOperation Mode = OnORttTripMin TRIPen05000789.vsdProgram = 3PhIEC05000789 V1 ENFigure 164: Simplified logic diagram for three phase tripLockout can be activated either by activating the input (SETLKOUT) orautomatically from trip input by setting AutoLock to On. A Lockout condition will beindicated by activation of the output (CLLKOUT). If lockout has been activated it canbe reset by activating the input (RSTLKOUT) or via the HMI.If TripLockout is set to On an active Lockout will result in a three-phase trip output.In this way if both AutoLock and TripLockout are set to On the trip will always bethree-phase and sealed in.13.1.7 Technical dataTable 278:SMPPTRC technical dataFunction Range or value AccuracyTrip action 3-ph -Timers (0.000-60.000) s ± 0.5% ± 10 ms13.2 Trip matrix logic TMAGGIO13.2.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberTrip matrix logic TMAGGIO - -13.2.2 FunctionalityThe 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to routetrip signals and other logical output signals to the tripping logics SMPPTRC andSPTPTRC or to different output contacts on the IED.1MRK 504 135-UEN A Section 13Logic373Technical manual