Table 316:B16IFCVI Output signalsName Type DescriptionOUT INTEGER Output value13.6.5 SettingsThe function does not have any parameters available in local HMI or Protection andControl IED Manager (PCM600)13.6.6 Monitored dataTable 317:B16IFCVI Monitored dataName Type Values (Range) Unit DescriptionOUT INTEGER - - Output value13.6.7 Operation principleThe Boolean 16 to integer conversion with logic node representation function(B16IFCVI) will transfer a combination of up to 16 binary inputs INx, where 1≤x≤16,to an integer. Each INx represents a value according to the table below from 0 to32768. This follows the general formula: INx = 2x-1 where 1≤x≤16. The sum of all thevalues on the activated INx will be available on the output OUT as a sum of the integervalues of all the inputs INx that are activated. OUT is an integer. When all INx (where1≤x≤16) are activated, that is = Boolean 1, it corresponds to that integer 65535 isavailable on the output OUT. The B16IFCVI function is designed for receiving theinteger input from a station computer - for example, over IEC 61850. If the BLOCKinput is activated, it will freeze the logical outputs at the last value.Values of each of the different OUTx from function block B16IFCVI for 1≤x≤16.The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block B16IFCVI.Name of input Type Default Description Value whenactivatedValue whendeactivatedIN1 BOOLEAN 0 Input 1 1 0IN2 BOOLEAN 0 Input 2 2 0IN3 BOOLEAN 0 Input 3 4 0IN4 BOOLEAN 0 Input 4 8 0IN5 BOOLEAN 0 Input 5 16 0IN6 BOOLEAN 0 Input 6 32 0IN7 BOOLEAN 0 Input 7 64 0IN8 BOOLEAN 0 Input 8 128 0IN9 BOOLEAN 0 Input 9 256 0Table continues on next page1MRK 504 135-UEN A Section 13Logic397Technical manual