The input of this GOOSE block must be linked in SMT by means ofa cross to receive the double point values.The implementation for IEC61850 quality data handling is restrictedto a simple level. If quality data validity is GOOD then theDATAVALID output will be HIGH. If quality data validity isINVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLDDATA then the DATAVALID output will be LOW.16.8 GOOSE function block to receive an integer valueGOOSEINTRCV16.8.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGOOSE function block to receive aninteger valueGOOSEINTRCV - -16.8.2 FunctionalityGOOSEINTRCV is used to receive an integer value using IEC61850 protocol viaGOOSE.16.8.3 Function blockIEC10000250-1-en.vsdGOOSEINTRCVBLOCK ^INTOUTDATAVALIDCOMMVALIDTESTIEC10000250 V1 ENFigure 243: GOOSEINTRCV function block16.8.4 SignalsTable 457:GOOSEINTRCV Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of function1MRK 504 135-UEN A Section 16Station communication545Technical manual