14.17.8 Technical dataTable 414:SSCBR Technical dataFunction Range or value AccuracyAlarm levels for open and closetravel time(0-200) ms ± 0.5% ± 25 msAlarm levels for number ofoperations(0 - 9999) -Setting of alarm for springcharging time(0.00-60.00) s ± 0.5% ± 25 msTime delay for gas pressurealarm(0.00-60.00) s ± 0.5% ± 25 msTime delay for gas pressurelockout(0.00-60.00) s ± 0.5% ± 25 ms14.18 Measurands for IEC 60870-5-103 I103MEAS14.18.1 Functionality103MEAS is a function block that reports all valid measuring types depending onconnected signals.The measurand reporting interval set for MMXU function blocks, using thexDbRepInt and xAngDbRepInt settings, must be coordinated with the event reportinginterval set for the IEC 60870-5-103 communication using setting CycMeasRepTime.1MRK 504 135-UEN A Section 14Monitoring511Technical manual