Function Range or value AccuracyApparent power, S 0.1 x Ur < U < 1.5 x Ur0.2 x Ir< I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr± 1.0% of S at S > SrApparent power, S Three phasesettingscos phi = 1 ± 0.5% of S at S > Sr± 0.5% of Sr at S ≤ SrPower factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur0.2 x Ir< I < 4.0 x Ir< 0.0214.2 Event Counter CNTGGIO14.2.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberEvent counter CNTGGIOS00946 V1 EN-14.2.2 FunctionalityEvent counter CNTGGIO has six counters which are used for storing the number oftimes each counter input has been activated.14.2.3 Function blockCNTGGIOBLOCKCOUNTER1COUNTER2COUNTER3COUNTER4COUNTER5COUNTER6RESETVALUE1VALUE2VALUE3VALUE4VALUE5VALUE6IEC09000090_1_en.vsdIEC09000090 V1 ENFigure 197: CNTGGIO function block14.2.4 SignalsTable 358:CNTGGIO Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionCOUNTER1 BOOLEAN 0 Input for counter 1COUNTER2 BOOLEAN 0 Input for counter 2COUNTER3 BOOLEAN 0 Input for counter 3COUNTER4 BOOLEAN 0 Input for counter 4Table continues on next page1MRK 504 135-UEN A Section 14Monitoring439Technical manual