5.3.4 SettingsTable 18:LEDGEN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OntRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance lengthtMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of adisturbanceTable 19:GRP1_LED1 Non group settings (basic)Name Values (Range) Unit Step Default DescriptionSequenceType Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S- - Follow-S Sequence type for LED 1, local HMI alarmgroup 1LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarmgroup 1 is offLabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarmgroup 1 is redLabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarmgroup 1 is yellowLabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarmgroup 1 is green5.4 LCD part for HMI function keys control module5.4.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLCD part for HMI Function Keys ControlmoduleFNKEYMD1 -FNKEYMD5- -5.4.2 Function blockFNKEYMD1^LEDCTL1 ^FKEYOUT1IEC09000327 V1 ENFigure 6: FNKEYMD1 function blockOnly the function block for the first button is shown above. There is a similar block forevery function button.Section 5 1MRK 504 135-UEN ALocal Human-Machine-Interface LHMI60Technical manual