Table 74:OOSPPAM (78) Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValueGroupsForwardR 0.00 - 1000.00 % Zb 0.01 1.00 Real part of total forward impedance for Z2, in% of VBase/(sqrt(3)*IBase)ForwardX 0.00 - 1000.00 % Zb 0.01 10.00 Imag. part of total forward impedance for Z2, in% of VBase/(sqrt(3)*IBase)InvertCTCurr NoYes- - No Invert current directionReverseR 0.00 - 1000.00 % Zb 0.01 1.00 Real part of source impedance behind relay, in% of VBase/(sqrt(3)*IBase)ReverseX 0.00 - 1000.00 % Zb 0.01 10.00 Imag. part of source impedance behind relay,in % of VBase/(sqrt(3)*IBase)Table 75:OOSPPAM (78) Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionStartAngle 90.0 - 130.0 Deg 0.1 110.0 Angle between two rotors to get the pick upsignal, in degTripAngle 15.0 - 90.0 Deg 0.1 60.0 Maximum rotor angle to allow trip signals, indeg7.4.6 Monitored dataTable 76:OOSPPAM (78) Monitored dataName Type Values (Range) Unit DescriptionVOLTAGE REAL - kV Magnitude of the measuredpositive-sequence voltage, inVCURRENT REAL - A Magnitude of the measuredpositive-sequence current, inAR REAL - % Real part of measuredpositive-sequence impedance% of VBase/(sqrt(3)*IBase)X REAL - % Imaginary part of measuredpositive-seq impedance % ofVBase/(sqrt(3)*IBase)ROTORANG REAL - deg Rotor angle as estimated bythe out-of-step functionUCOSPHI REAL - kV Estimated Ucos(Phi) voltageduring pole slip, in VSection 7 1MRK 502 048-UUS AImpedance protection176Technical manual