Name Type DescriptionV1RANG INTEGER V1 Magnitude rangeV1ANGL REAL U1 AngleV2 REAL U2 AmplitudeV2RANG INTEGER V2 Magnitude rangeV2ANGL REAL U2 Angle14.1.6.4 SettingsTable 367:VMSQI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Disable/Enable Operation3V0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %s3V0Min 0 - 2000000 V 1 0 Minimum value3V0Max 0 - 2000000 V 1 318000 Maximum value3V0RepTyp CyclicDead bandInt deadband- - Dead band Reporting type3V0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is commonfor all limits3V0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sV1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sV1Min 0 - 2000000 V 1 0 Minimum valueV1Max 0 - 2000000 V 1 106000 Maximum valueV1RepTyp CyclicDead bandInt deadband- - Dead band Reporting typeV1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sV2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sV2Min 0 - 2000000 V 1 0 Minimum valueV2Max 0 - 2000000 V 1 106000 Maximum valueV2RepTyp CyclicDead bandInt deadband- - Dead band Reporting typeV2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is commonfor all limitsV2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %s1MRK 502 048-UUS A Section 14Monitoring523Technical manual