14.16.3 Function blockANSI09000128-1-en.vsdSSIML (71)BLOCKBLK_ALMLEVELTEMPLVL_ALMLEVEL_LOSET_L_LOSET_T_LORESET_LOLEVELLVL_ALMLVL_LOTEMPTEMP_ALMTEMP_LOANSI09000128 V1 ENFigure 263: SSIML (71) function block14.16.4 SignalsInputs LEVEL and TEMP together with settings LevelAlmLimit,LevelLOLimit, TempAlarmLimit and TempLOLimit are not supported inthis release of 650 series.Table 424:SSIML (71) Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionBLK_ALM BOOLEAN 0 Block all the alarmsLEVEL REAL 0.0 Level input from CBTEMP REAL 0.0 Temperature of the insulation medium from CBLVL_ALM BOOLEAN 0 Level alarm signalLEVEL_LO BOOLEAN 0 Level lockout signalSET_L_LO BOOLEAN 0 Set level lockoutSET_T_LO BOOLEAN 0 Set temperature lockoutRESET_LO BOOLEAN 0 Reset level and temperature lockoutTable 425:SSIML (71) Output signalsName Type DescriptionLEVEL REAL Level service valueLVL_ALM BOOLEAN Level below alarm levelLVL_LO BOOLEAN Level below lockout levelTEMP REAL Temperature of the insulation mediumTEMP_ALM BOOLEAN Temperature above alarm levelTEMP_LO BOOLEAN Temperature above lockout levelSection 14 1MRK 502 048-UUS AMonitoring600Technical manual