Name Values (Range) Unit Step Default DescriptionInfNo_2 1 - 255 - 1 2 Information number for output 2 (1-255)InfNo_3 1 - 255 - 1 3 Information number for output 3 (1-255)InfNo_4 1 - 255 - 1 4 Information number for output 4 (1-255)InfNo_5 1 - 255 - 1 5 Information number for output 5 (1-255)InfNo_6 1 - 255 - 1 6 Information number for output 6 (1-255)InfNo_7 1 - 255 - 1 7 Information number for output 7 (1-255)InfNo_8 1 - 255 - 1 8 Information number for output 8 (1-255)12.12 Function commands generic for IEC 60870-5-103I103GENCMD12.12.1 FunctionalityI103GENCMD is used for transmitting generic commands over IEC 60870-5-103. Thefunction has two outputs signals CMD_OFF and CMD_ON that can be used to implementdouble-point command schemes.The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2 steadyON/OFF outputs. The ON output is pulsed with a command with value 2, while the OFFoutput is pulsed with a command value 1. If in steady mode is ON asserted and OFFdeasserted with command 2 and vice versa with command 1. The I103GENCMD isretained, and a command in steady mode will be reissued on restart.The standard does not define the use of values 0 and 3. However, when connected to aswitching device, these values are transmitted.12.12.2 Function blockIEC10000285-1-en.vsdI103GENCMDBLOCK ^CMD_OFF^CMD_ONIEC10000285 V1 ENFigure 211: I103GENCMD function blockSection 12 1MRK 502 048-UUS AControl464Technical manual