14.12.6 Monitored dataTable 410:MVGGIO Monitored dataName Type Values (Range) Unit DescriptionVALUE REAL - - Magnitude of deadband valueRANGE INTEGER 0=Normal1=High2=Low3=High-High4=Low-Low- Range14.12.7 Operation principleUpon receiving an analog signal at its input, IEC61850 generic communication I/Ofunctions (MVGGIO) will give the instantaneous value of the signal and the range, asoutput values. In the same time, it will send over IEC 61850-8-1 the value, to other IEC61850 clients in the substation.14.13 Measured value expander block MVEXP14.13.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberMeasured value expander block MVEXP - -14.13.2 FunctionalityThe current and voltage measurements functions (CVMMXN, CMMXU, VMMXU andVNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI)and IEC 61850 generic communication I/O functions (MVGGIO) are provided withmeasurement supervision functionality. All measured values can be supervised with foursettable limits: low-low limit, low limit, high limit and high-high limit. The measure valueexpander block MVEXP has been introduced to enable translating the integer outputsignal from the measuring functions to 5 binary signals: below low-low limit, below lowlimit, normal, above high limit or above high-high limit. The output signals can be usedas conditions in the configurable logic or for alarming purpose.1MRK 502 048-UUS A Section 14Monitoring591Technical manual