12.2.4.2 SettingsTable 222:SXSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptiontStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to moveafter a commandtIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate positionAdaptivePulse Not adaptiveAdaptive- - Not adaptive Output resets when a new correct end positionis reachedtOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open commandtClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close commandSwitchType Load BreakDisconnectorGrounding SwitchHS Groundg.Switch- - Disconnector 1=LoadBreak,2=Disconnector,3=GroundSw,4=HighSpeedGroundSwSuppressMidPos DisabledEnabled- - Enabled Mid-position is suppressed during the timetIntermediate12.2.5 Bay control QCBAY12.2.5.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberBay control QCBAY - -12.2.5.2 FunctionalityThe Bay control QCBAY function is used together with Local remote and local remotecontrol functions to handle the selection of the operator place per bay. QCBAY alsoprovides blocking functions that can be distributed to different apparatuses within the bay.12.2.5.3 Function blockQCBAYLR_OFFLR_LOCLR_REMLR_VALIDBL_UPDBL_CMDPSTOUPD_BLKDCMD_BLKDLOCREMIEC09000080_1_en.vsdIEC09000080 V1 ENFigure 170: QCBAY function block1MRK 502 048-UUS A Section 12Control367Technical manual