Table 268:VSGGIO Output signalsName Type DescriptionBLOCKED BOOLEAN The function is active but the functionality is blockedPOSITION INTEGER Position indication, integerPOS1 BOOLEAN Position 1 indication, logical signalPOS2 BOOLEAN Position 2 indication, logical signalCMDPOS12 BOOLEAN Execute command from position 1 to position 2CMDPOS21 BOOLEAN Execute command from position 2 to position 112.5.5 SettingsTable 269:VSGGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Disable/Enable OperationCtlModel Dir NormSBO Enh- - Dir Norm Specifies the type for control model accordingto IEC 61850Mode SteadyPulsed- - Pulsed Operation modetSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute signalstPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght12.5.6 Operation principleSelector mini switch (VSGGIO) function can be used for double purpose, in the same wayas switch controller (SCSWI) functions are used:• for indication on the single line diagram (SLD). Position is received through theIPOS1 and IPOS2 inputs and distributed in the configuration through the POS1 andPOS2 outputs, or to IEC 61850 through reporting, or GOOSE.• for commands that are received via the local HMI or IEC 61850 and distributed in theconfiguration through outputs CMDPOS12 and CMDPOS21.The output CMDPOS12 is set when the function receives a CLOSE command fromthe local HMI when the SLD is displayed and the object is chosen.The output CMDPOS21 is set when the function receives an OPEN command fromthe local HMI when the SLD is displayed and the object is chosen.Section 12 1MRK 502 048-UUS AControl452Technical manual