14.24 Supervison status for IEC 60870-5-103 I103SUPERV14.24.1 FunctionalityI103SUPERV is a function block with defined functions for supervision indications inmonitor direction. This block includes the FunctionType parameter, and the informationnumber parameter is defined for each output signal.14.24.2 Function blockIEC10000293-1-en.vsdI103SUPERVBLOCK32_MEASI33_MEASU37_IBKUP38_VTFF46_GRWA47_GRALIEC10000293 V1 ENFigure 282: I103SUPERV function block14.24.3 SignalsTable 445:I103SUPERV Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting32_MEASI BOOLEAN 0 Information number 32, measurand supervision of I33_MEASU BOOLEAN 0 Information number 33, measurand supervision of U37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up protection38_VTFF BOOLEAN 0 Information number 38, fuse failure VT46_GRWA BOOLEAN 0 Information number 46, group warning47_GRAL BOOLEAN 0 Information number 47, group alarm14.24.4 SettingsTable 446:I103SUPERV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)Section 14 1MRK 502 048-UUS AMonitoring626Technical manual