Table 16:GRP1_LED1 Input signalsName Type Default DescriptionHM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group 1HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group 1Table 17:LEDGEN Output signalsName Type DescriptionNEWIND BOOLEAN New indication signal if any LED indication input is setACK BOOLEAN A pulse is provided when the LEDs are acknowledged5.3.4 SettingsTable 18:LEDGEN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OntRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance lengthtMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of adisturbanceTable 19:GRP1_LED1 Non group settings (basic)Name Values (Range) Unit Step Default DescriptionSequenceType Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S- - Follow-S Sequence type for LED 1, local HMI alarmgroup 1LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm group 1is offLabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm group 1is redLabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm group 1is yellowLabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm group 1is greenSection 5 1MRK 502 048-UUS ALocal Human-Machine-Interface LHMI66Technical manual