Table 273:SPC8GGIO Output signalsName Type DescriptionOUT1 BOOLEAN Output 1OUT2 BOOLEAN Output 2OUT3 BOOLEAN Output 3OUT4 BOOLEAN Output 4OUT5 BOOLEAN Output 5OUT6 BOOLEAN Output 6OUT7 BOOLEAN Output 7OUT8 BOOLEAN Output 812.7.5 SettingsTable 274:SPC8GGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledLatched1 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 1tPulse1 0.01 - 6000.00 s 0.01 0.10 Output 1 Pulse TimeLatched2 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 2tPulse2 0.01 - 6000.00 s 0.01 0.10 Output 2 Pulse TimeLatched3 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 3tPulse3 0.01 - 6000.00 s 0.01 0.10 Output 3 Pulse TimeLatched4 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 4tPulse4 0.01 - 6000.00 s 0.01 0.10 Output 4 Pulse TimeLatched5 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 5tPulse5 0.01 - 6000.00 s 0.01 0.10 Output 5 Pulse TimeLatched6 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 6tPulse6 0.01 - 6000.00 s 0.01 0.10 Output 6 Pulse TimeLatched7 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 7tPulse7 0.01 - 6000.00 s 0.01 0.10 Output 7 Pulse TimeLatched8 PulsedLatched- - Pulsed Setting for pulsed/latched mode for output 8tPulse8 0.01 - 6000.00 s 0.01 0.10 Output 8 pulse timeSection 12 1MRK 502 048-UUS AControl456Technical manual