5 Categories and Use of Basic Application InstructionsDVP-PM Application Manual 5-27SMOVM1168D10 K2 D20 K3K410 310 2101100103102101100No variation No variationD10(BIN 16bit)D10(BCD 4 digits)D20(BIN 16bit)D20(BCD 4 digits)Shift moveAuto conversionAuto conversionM1001X0If D10 = K1234, D20 = K5678 before execution, D10 remains unchanged and D20 = K5128 after execution.Program example 2:When M1168 = ON (in BIN mode) and SMOV instruction is in use, D10 and D20 will not be converted in BCD formatbut be moved in BIN format (4 digits as a unit)..SMOVM1168D10 K2 D20 K3K4No variation No variationD10(BIN 16bit)D20(BIN 16bit)Shift moveM1000X0Digit 4 Digit 3 Digit 2 Digit 1Digit 4 Digit 3 Digit 2 Digit 1If D10 = H1234, D20 = H5678 before execution, D10 remains unchanged and D20 = H5128 after executionProgram example 3:1. This instruction can be used to combine the DIP switches connected to the input terminals without continuousnumbers.2. Move the 2 digits of the right DIP switch (X27~X20) to the 2 digits of D2, and the 1 digit of the DIP switch(X33~X30) to the 1 st digit of D1.