3 Functions of Devices in DVP-PMDVP-PM Application Manual 3-9How to designate SV: The actual set time in the timer = timer resolutiont × set value1. Designating constant K: set a K value as SV directly2. Designating D register: designate a data register in TMR instruction and the timer will take the value in the registeras the SV.3.7 Numbering and Functions of Counters [C] No. of counters (in decimal):20PM:16-bit count up C0 ~ C199, 200 points32-bit count up/down C208 ~ C255, 48 points (accumulative)Total 248 pointsThe associated contact = ONwhen counter reaches presetvalueCounterC32-bit high speed C200, C204 Total 2 pointsz Input point of C200:MPGA0/MPGB0z Input point of C204:MPGA1/MPGB110PM:16-bit count up C0 ~ C199, 200 points32-bit count up/down C220 ~ C255, 36 points (accumulative)Total 236 pointsThe associated contact = ONwhen counter reaches presetvalueCounterC32-bit high speed C200, C204, C208, C212, C216, C220.6 points Total 6 pointsz Input point of C200:X0/X1z Input point of C204:X2/X3z Input point of C208:X4/X5z Input point of C212:X6/X7z Input point of C216:X10+ / X10- / X11+ / X11-z Input point of C220:X12+ / X12- / X13+ / X13- Features of counter:16-bit counter 32-bit counterType General purpose General purposeCounting direction Count up Count up, count downRange of SV 0 ~ 32,767 -2,147,483,648 ~ +2,147,483,647Designating SV Constant K or data register D Constant K or data register D (2 consecutive words)Operation when SVis reached Counting will stop after SV is reached. Counting will continue after SV is reached.Output contact The associated contact = ON and latched whencounter reaches SV.The associated contact = ON and latched whencounter reaches preset value in counting-up modeThe associated contact is reset as OFF when counterreaches preset value in counting-down modeReset When RST instruction is executed, PV of counter is cleared and the contact is OFF.Contact Action Contacts act when the scan is completed. Contacts act when the scan is completed.