12 Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05• Maximum Relative Humidity: 5–95%, noncondensingThe IAC-T operating environment must meet the weight requirements shown in Table 1 and the sizerequirements shown in Figure 5 through Figure 7. Dimensions are in millimeters (inches).Table 1. IAC-T WeightsModelWeight kg (lb)Shipping Installed Point LoadingEaton 93PM 50 kW IAC-T – Four MOBs with MIS andMBP230 (506) 208 (458) 4 at 52.0 (114.5)Eaton 93PM 100 kW IAC-T – Four MOBs with MIS andMBP230 (506) 208 (458) 4 at 52.0 (114.5)The IAC-T uses convection cooling to regulate internal component temperature. Air inlets are in the front of thecabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in back ofthe cabinet for proper air circulation. The clearances required around the IAC-T are shown in Table 2.Table 2. IAC-T Cabinet ClearancesFrom Top of Cabinet with Rear Exhaust Option 304.8 mm (8") working spaceFrom Top of Cabinet with Top Exhaust Option 304.8 mm (8") minimum clearance for ventilationFrom Front of Cabinet 914.4 mm (36") working spaceFrom Back of Cabinet with Top Exhaust Option None RequiredFrom Back of Cabinet with Rear Exhaust Option 203.2 mm (8") minimum clearance for ventilationFrom Back of Cabinet – Seismic Installation 914.4 mm (36") working spaceFrom Right Side of Cabinet None RequiredFrom Left Side of Cabinet None RequiredInstallation Plan and Unpacking