24 Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05Table 13. External Input Power Cable Terminations for the Eaton 93PM 50 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0Parallel Configurations – with MIS (Continued)Terminal Function Terminal FunctionNumber and Size ofPressure Termination(AWG or kcmil)TighteningTorque Nm (lbin) Size Screw and TypeMOB3–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB 4 fromUPS 4 (if installed)MOB4–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB4–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB4–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Output to CriticalLoad(1+1)MIS– 2A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMIS– 4B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMIS– 6C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexAC Output to CriticalLoad(2+0 and 2+1)MIS– 2A Phase A 1 – 4–4/0 13.5 (120) 5/16” HexMIS– 4B Phase B 1 – 4–4/0 13.5 (120) 5/16” HexMIS– 6C Phase C 1 – 4–4/0 13.5 (120) 5/16” HexAC Output to CriticalLoad(3+0, 3+1, and 4+0)MIS– 2A Phase A 1 – 4–350 28.2 (250) 5/16” HexMIS– 4B Phase B 1 – 4–350 28.2 (250) 5/16” HexMIS– 6C Phase C 1 – 4–350 28.2 (250) 5/16” HexBuilding and LoadGroundTBG Ground 6 – 14–1/0 5.1 (45) SlottedFigure 21, Figure 22, andFigure 23 show the location of the IAC-T power cable terminals.Table 14. External Input Power Cable Terminations for the Eaton 93PM 50 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0Parallel Configurations – with MIS and MBPTerminal Function Terminal FunctionNumber and Size ofPressure Termination(AWG or kcmil)TighteningTorque Nm(lb in)Size Screw andTypeAC Input to MOB 1 fromUPS 1MOB1–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB1–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB1–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexGND Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB 2 fromUPS 2MOB2–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB2–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB2–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedInstallation Plan and Unpacking