Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05 356. Remove the hardware loosened in Step 4.7. Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recyclethe pallet skids and hardware in a responsible manner.CAUTIONCABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinetmust be lowered by the jacking bolts before the supports can be removed.8. Carefully and evenly lower the cabinet by turning each jacking bolt consecutively two full turns(maximum) until the casters contact the floor and the cabinet is no longer supported by the jacking bolts.9. After the IAC-T is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in aresponsible manner.10. Remove the cabinet support bolts fastening the front, rear, and side cabinet supports together and removethe side supports (see Figure 9).11. Remove the cabinet mounting bolts holding the front and rear supports to the cabinet base (see Figure 9).12. Recycle the bolts along with the support brackets in a responsible manner.13. Close the door and secure the latch.14. If the leveling feet are not retracted, turn all four leveling feet until they are retracted as far into the cabinetas possible.15. If line-up-and-match installation, remove the rectangular knockout on the bottom front side of the UPS andthe IAC-T (see Figure 10).NOTE In line-up-and-match installations, the IAC-T and UPS cabinets should be located asshown in Figure 2, Figure 3, or Figure 4.CAUTIONTo prevent tipping when rolling the cabinet and damage to the front door, push the cabinet from the rearwhenever possible. Do not push the cabinet from the sides.16. Roll the cabinet to the final installation location.17. Lower the cabinet feet and using a level, adjust the cabinet height accordingly until the cabinet is level.18. Locate the top splice bracket shipped with the IAC-T.19. Remove the screws along each adjacent cabinet top panel securing the top panels. Retain the hardwarefor later use.20. Install the top splice bracket between the adjacent cabinet and secure the tie strap with retained hardware.NOTE Optional front and back floor mounting brackets are available to order for permanentlymounting the IAC-T. Left and right side floor mounting brackets and mounting hardwareto permanently mount the IAC-T are customer-supplied.21. If permanently mounting the IAC-T using the left and right side floor mounting brackets, proceed toStep 22; if using the front and rear floor mounting brackets, proceed to Step 25; otherwise, proceed toStep 28.22. Using customer-supplied mounting bolts, install the customer-supplied floor mounting brackets to the leftand right side of the UPS with the angle facing outward.Installation