Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05 25Table 14. External Input Power Cable Terminations for the Eaton 93PM 50 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0Parallel Configurations – with MIS and MBP (Continued)Terminal Function Terminal FunctionNumber and Size ofPressure Termination(AWG or kcmil)TighteningTorque Nm(lb in)Size Screw andTypeAC Input to MOB 3 fromUPS 3 (if installed)MOB3–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB3–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB3–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB 4 fromUPS 4 (if installed)MOB4–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB4–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB4–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MaintenanceBypass(1+1, 2+0, and 2+1)MBP–1A Phase A 1 – 4–4/0 13.5 (120) 5/16” HexMBP–3B Phase B 1 – 4–4/0 13.5 (120) 5/16” HexMBP–5C Phase C 1 – 4–4/0 13.5 (120) 5/16” HexAC Input to MaintenanceBypass(3+0, 3+1, and 4+0)MBP–1A Phase A 1 – 4–350 28.2 (250) 5/16” HexMBP–3B Phase B 1 – 4–350 28.2 (250) 5/16” HexMBP–5C Phase C 1 – 4–350 28.2 (250) 5/16” HexAC Output to CriticalLoadLoad Bus A Phase A 2 – 6–350 42 (375) 5/16” HexLoad Bus B Phase B 2 – 6–350 42 (375) 5/16” HexLoad Bus C Phase C 2 – 6–350 42 (375) 5/16” HexBuilding and LoadGroundTBG Ground 6 – 14–1/0 5.1 (45) SlottedTable 15. External Input Power Cable Terminations for the Eaton 93PM 100 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0Parallel Configurations – No MIS or MBPTerminalFunction Terminal FunctionNumber and Size ofPressure Termination(AWG or kcmil)TighteningTorque Nm (lbin)Size Screw andTypeAC Input to MOB1 from UPS 1MOB1–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB1–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB1–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexGND Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB2 from UPS 2MOB2–1A Phase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB2–3B Phase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB2–5C Phase C 1 – 4–4/0 13.5 (120) 3/16” HexInstallation Plan and Unpacking