28 Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05Table 17. External Input Power Cable Terminations for the Eaton 93PM 100 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0Parallel Configurations – with MIS and MBP (Continued)Terminal FunctionTermi-nalFunc-tionNumber and Size ofPressure Termination(AWG or kcmil)TighteningTorque Nm(lb in)Size Screw andTypeMOB1–5CPhase C 1 – 4–4/0 13.5 (120) 3/16” HexGND Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB 2 from UPS 2MOB2–1APhase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB2–3BPhase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB2–5CPhase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB 3 from UPS 3 (ifinstalled)MOB3–1APhase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB3–3BPhase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB3–5CPhase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to MOB 4 from UPS 4 (ifinstalled)MOB4–1APhase A 1 – 4–4/0 13.5 (120) 3/16” HexMOB4–3BPhase B 1 – 4–4/0 13.5 (120) 3/16” HexMOB4–5CPhase C 1 – 4–4/0 13.5 (120) 3/16” HexTBG Ground 2 – 14– 1/0 5.1 (45) SlottedAC Input to Maintenance Bypass(1+1)MBP–1APhase A 1 – 4–4/0 13.5 (120) 5/16” HexMBP–3BPhase B 1 – 4–4/0 13.5 (120) 5/16” HexMBP–5CPhase C 1 – 4–4/0 13.5 (120) 5/16” HexAC Input to Maintenance Bypass(2+0 and 2+1)MBP–1APhase A 1 – 4–350 28.2 (250) 5/16” HexMBP–3BPhase B 1 – 4–350 28.2 (250) 5/16” HexMBP–5CPhase C 1 – 4–350 28.2 (250) 5/16” HexAC Input to Maintenance Bypass(3+0, 3+1, and 4+0)MBP–1APhase A 1 – 2 stud bus barmounting12.2 (108) M8 Stud with 13 mmHex NutInstallation Plan and Unpacking