478 OperatingMANUAL CEAG AUtoMAtiC tEst systEM At-s+ 40071860177 (C) December 2016 www.ceag.de8 4 3 Menu 3: “Basic settings”Overview:Main menuTest & status menuBlock,resetBasic settingsDLS/TLS SetupCircuit setupLuminaire setupMemory cardMenu 3LanguageDate & timeFunctiontestDelay time mains returnManual resetSelective EmgcyOper.Relay setupBuzzer setupDisplay setupTimer setupSubstation setupConnection to BMSFunction keysOptional inputsSerialnumber & typePassword protectionDaylight saving timeService info Selection ofmenu optionswith thekeys :confirm selec-tion -cel and returnto the previousmenu (anychangesentered aresaved) : canceland return tothe previousmenu (anychanges en-tered are notsaved)flashing inputpromptSetting the system time (current date andtime) for the internal clock of the CU S+control module.AT-S+ autosync:program to „yes“ only at one station of agroup All other stations are synchroniseddaily via this. Use the keys to toggle between“Language: National language” 2)and “Language: english” Finish and return to Menu 3 with2) Can only be selected when memorycard is inserted.Setting the start (date and time) of thefirst function test and the intervals (1 to14 days) of subsequent function tests(factory setting: all 7 days).Setting the start-up time of the FT in 5ssteps (factory setting: 300s)For all luminaires with “End of line” cutoff (EoL). The currently selectedMenu 3.1: language is displayed 1)1) Setting on delivery/initial commission-ing Menu 3.2: Menu 3.3:Important note!These settings are the basis for alllog book entries and (synchronised)test of the system!Important note!For synchronized date, time and thefunction test all distributor in Mas-ter/Slave modus must programmedand connected with a CG-S bus line.ATTENTION!In the operation mode Master/Slave youcan not connect a CGVision.Date & TimeWe 11.01.12 12:00AT-S+ autosync.: yesF-Test Date&TimeWe 05.12.12 12:00FT start-up time 300s Interval in days: 07Note!Fall back language for controller re-set or after the installation of a newCU S+ is allways english Select the date and time positionswith Change with Finish with This request follows: Enter “OK” synchronises the clockof all connected substations in onegroupSubstationsynchronise ?Menu = no OK = yesSubstationsynchronise ?Menu = no OK = yes Select the input position for date,time, intervals (in days) and FT start-uptime (in 5s) with Change with Finish with This request follows:LanguageDate & timeFunctiontestDelay time mains returnetc.LanguageDate & timeFunctiontestDelay time mains returnetc.LanguageDate & timeFunctiontestDelay time mains returnetc.LanguageDate & timeFunctiontestDelay time mains returnetc.Setting the time (1 ... 99 minutes) whichthe emergency light remains on after mainssupply is restored. Select 1 ... 99 minutes with the keys Finish and return to Menu 3 with Menu 3.4: Delay time on mainsreturn inminutes 10