93. Technical DataMANUAL CEAG AUtoMAtiC tEst systEM At-s+ 40071860177 (C) December 2016 www.ceag.de400250 6003.4 Data Sheet for AT-S+ C0Type of system AT-S+ C0Construction Sheet steel cabinet with partialviewing window in the doorHeight 600 mmWidth 400 mmDepth 250 mmWeight approx. 38 kgInsulation class IDegree of protection IP 54External painting Structure powder laquer RAL 7035light greyCable entry at the top (prepunched roof sheeting)Hinge rightMains rated voltage 230V AC, 50/60 HzAmbient temperature operation (pleaseattend to the attachted operating andinstallation instructions)-5°C up to +35°CMains feed in (max. 4 mm²) X8Addresses optional places DLS-3Ph,(max. 2.5 mm²)customisedConnection to ext. control switch(max. 4 mm²)**X1.1.S1-S2Connection to 24V current loop(max. 4 mm²)**X1.1.S3-S4Connection to potential-free signalcontacts (max. 4 mm²)**X1.1.C0 14; 12; 24; 22; 34; 32/C144; 54Connection to CG-S Bus (max. 4 mm²)** X1.1.A-BConnection to RS485 Bus (max. 4 mm²)** X1.1.RS485.A-BConnection to 24V analog output(max. 4 mm²)**X1.1.+24V Out--24V OutConnection to 24V analog input(max. 4 mm²)**X1.1 Z11, Z12, Z21, Z22. Z31, Z32,Z41, Z42Optional:Addresses optional places DLS-3Ph(max. 2.5 mm²)customisedConnection to ext. control switch(max. 4 mm²)**X2.1.S1-S2Connection to 24V current loop(max. 4 mm²)**X2.1.S3-S4Connection to potential-free signalcontacts (max. 4 mm²)**X2.1.C0 14; 12; 24; 22; 34; 32/C144; 54Connection to CG-S Bus (max. 4 mm²)** X2.1.A-BConnection to RS485 Bus (max. 4 mm²)** X2.1.RS485.A-BConnection to 24V analog output(max. 4 mm²)**X2.1.+24V Out--24V OutConnection to 24V analog input(max. 4 mm²)**X2.1 Z11, Z12, Z21, Z22. Z31, Z32,Z41, Z42** Two strands to max. 0.5 mm² with twin wire end sleeve can be clamped ina clamp spring terminal.Interior side view, left Interior side view, rightFront view, open400250 600