488 OperatingMANUAL CEAG AUtoMAtiC tEst systEM At-s+ 40071860177 (C) December 2016 www.ceag.deSelect the system or fault messages onwhich relays 1 to 3 change over for sig-nalling contacts 1 to 3 (“picked up” and“dropped out” states).These settings can be used to send infor-mation about the operational status of thesystem to a control centre (e.g. with CEAGF3 remote indicator).A standard setting according to DIN VDE(see Appendix B) can be selected usingthe “Load defaults” option at the end ofthis menu. Select the relay number (1 to 3) withkeys Highlight the events with keys Select between relay switches ()and relay does not switch (no ) withthe key Finish and return to Menu 3 withActivating / deactivating the “Manualreset” option(see Menu 2.3 “Manual reset”) Toggle between “activated” and “de-activated” with Finish and return to Menu 3 with Menu 3.5: Menu 3.7:Manual resetdeactivatedActivating / deactivating the “Selectiveemerg light” option Toggle between “activated” and “de-activated” with Finish and return to Menu 3 with Menu 3.6:Note:See also menu option 1.6 “Relay status” inmenu 1 “Test & status menu”.Selective emerg lightdeactivatedRelais 1ReadyMains failure S3/S4 Mains failure DLS/3PHExt. source error Circuit fault Luminaire fault Device fault Ext. source activeISO error Function testInvert contactLoad defaultsNote:With selective emergency light (only available in conjunction with DLS/3Ph bus mod-ules) each individual circuit must be assigned to a DLS/3Ph bus module to activatethe emergency light function. See Menu 5.4The functions «delay on mains return », «manual reset» and «selective emergencylighting» can be combined on circuits.Delay time mains returnManual resetSelective EmgcyOper.Relay setupetc.Date & timeFunctiontestDelay time mains returnManual resetetc.FunctiontestDelay time mains returnManual resetSelective EmgcyOper.etc.Overview:Main menuTest & status menuBlock,resetBasic settingsDLS/TLS SetupCircuit setupLuminaire setupMemory cardMenu 3LanguageDate & timeFunctiontestDelay time mains returnManual resetSelective EmgcyOper.Relay setupBuzzer setupDisplay setupTimer setupSubstation setupConnection to BMSFunction keysOptional inputsSerialnumber & typePassword protectionDaylight saving timeService info Selection ofmenu optionswith thekeys :confirm selec-tion -cel and returnto the previousmenu (anychangesentered aresaved) : canceland return tothe previousmenu (anychanges en-tered are notsaved)flashing inputprompt