66AppendixMANUAL CEAG AUtoMAtiC tEst systEM At-s+ 40071860177 (C) December 2016 www.ceag.deV-CG-SB Monitoring modulewith DALI control inputUV-ASwitch-/dimming unite.g. day light sensorexternal DALI-controllerDALI-Busincl. DALI-EVGincl. DALI-EVGincl. DALI-EVGmax. 1m!V-CG-SUW Monitoring modulewith change over unit230VRequirements for connecting of electronic controlgears in fluorescent lamps or electronic control gearsfor LEDs to AT-S+ systemsATTENTION!Care must be taken to ensure that only control gearswith sinusoidal current consumption are used incombination with the new AT-S+ system Thereforeall control gears must be complied with „Limit Valuesfor Devices of Class C“ according to DIN EN 61000-3-2Point 7 3 a )Ballasts for discharge lamps with an input power of≤ 25 W are regulated according to DIN EN 61000-3-2Point 7 3 b) These limit values are not sufficient undercertain conditions Thus for these devices as well, aconfirmation according to EN 61000-3-2 Point 7 3 a ) ismandatoryLikewise, for all LED control gears a confirmationaccording to EN 61000-3-2 Point 7 3 a ) is also man-datory although LED drivers in this respect have notbeen standardized until nowBackground: In AC operation control gears ≤ 25 W aswell as LED control gears can generate current dis-tortions A clear fault detection is not possible and2 different function tests could generate 2 differentresults Our own control gears of the V…-series aresuitable for AT-S+ systems independently of the condi-tions specified above