GE Multilin G30 Generator Protection System 5-555 SETTINGS 5.2 PRODUCT SETUP5The XCBR1 SYNCCHECK CLS setting is used to supervise a close command with a synchrocheck condition within XCBRlogical node. If a Close with SynchroCheck is requested (through a SelectWithValue service) and the SynchroCheck condi-tion is not satisfied, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-synchrocheck.The XCBR1 INTERLOCK OPN/CLS settings are used to assign an operand, which is linked into the EnaOpn or EnaClsINTERLOCKED inputs respectively of the XCBR. When this operand is asserted, XCBR logical node inhibits execution ofthe open and close commands respectively. If select before operate (SBO) with Extended Security is requested and Inter-lock condition exists, the UR responds with a Negative response (-Rsp) with the Reason Code Blocked-by-interlocking.The XCBR1 Pos ctlModel setting is used to select control model per IEC 61850-7-3. The following control models are sup-ported by URs:0 — Status only1 — Direct control with normal security (direct-operate)2 — SBO control with normal security (operate-once)3 — Direct control with enhanced security (direct-operate)4 — SBO control with enhanced security (operate-once)See IEC 61850-7-2 for complete details on these control models.The XCBR1 Pos sboTimeout setting is used to select SBO timeout value. To be successful, the IEC 61850 "operate" com-mand must be executed after the "select" command within the XCBR1 Pos sboTimeout setting value.The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR isrestarted:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XSWI CONFIGURATIONThe CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate byopening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switchoperation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net-work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLANfunctionality. XSWI CONFIGURATIONXSWI1 ST.LOC OPERANDOffRange: FlexLogic operandMESSAGE XSWI2 ST.LOC OPERANDOffRange: FlexLogic operandMESSAGE XSWI3 ST.LOC OPERANDOffRange: FlexLogic operand↓MESSAGE XSWI24 ST.LOC OPERANDOffRange: FlexLogic operandMESSAGE CLEAR XSWI1 OpCnt:NoRange: No, YesMESSAGE CLEAR XSWI2 OpCnt:NoRange: No, YesMESSAGE CLEAR XSWI3 OpCnt:NoRange: No, Yes↓MESSAGE CLEAR XSWI24 OpCnt:NoRange: No, YesNOTE