GE Multilin G30 Generator Protection System B-63APPENDIX B B.4 MEMORY MAPPINGBC3E8 ...Repeated for Virtual Output 88C3F0 ...Repeated for Virtual Output 89C3F8 ...Repeated for Virtual Output 90C400 ...Repeated for Virtual Output 91C408 ...Repeated for Virtual Output 92C410 ...Repeated for Virtual Output 93C418 ...Repeated for Virtual Output 94C420 ...Repeated for Virtual Output 95C428 ...Repeated for Virtual Output 96Mandatory (Read/Write Setting or Command)C430 Test Mode Function 0 to 2 --- 1 F245 0 (Disabled)C431 Force VFD and LED 0 to 1 --- 1 F126 0 (No)C432 Test Mode Initiate 0 to 4294967295 --- 1 F300 1Clear Commands (Read/Write)C434 Clear All Relay Records Command 0 to 1 --- 1 F126 0 (No)Mandatory (Read Only)C435 DSP Advanced Diagnostics Active 0 to 1 -- 1 F126 0 (No)C436 Synchrophasor Feature Active 0 to 1 -- 1 F126 0 (No)Mandatory (Read/Write Command)C437 Relay Reboot Command 0 to 1 --- 1 F126 0 (No)C438 Save Volatile Data 0 to 1 --- 1 F126 0 (No)Clear Records (Read/Write Setting)C452 Clear User Fault Reports Operand 0 to 4294967295 --- 1 F300 0C454 Clear Event Records Operand 0 to 4294967295 --- 1 F300 0C456 Clear Oscillography Operand 0 to 4294967295 --- 1 F300 0C458 Clear Data Logger Operand 0 to 4294967295 --- 1 F300 0C468 Clear Energy Operand 0 to 4294967295 --- 1 F300 0C46C Clear Unauthorized Access Operand 0 to 4294967295 --- 1 F300 0C470 Clear Platform Direct Input/Output Statistics Operand 0 to 4294967295 --- 1 F300 0C472 Reserved (13 items) --- --- --- F001 0Platform Direct Outputs (Read/Write Setting) (32 modules)C600 Direct Output 1 Operand 0 to 4294967295 --- 1 F300 0C602 Direct Output 1 Events 0 to 1 --- 1 F102 0 (Disabled)C603 ...Repeated for Direct Output 2C606 ...Repeated for Direct Output 3C609 ...Repeated for Direct Output 4C60C ...Repeated for Direct Output 5C60F ...Repeated for Direct Output 6C612 ...Repeated for Direct Output 7C615 ...Repeated for Direct Output 8C618 ...Repeated for Direct Output 9C61B ...Repeated for Direct Output 10C61E ...Repeated for Direct Output 11C621 ...Repeated for Direct Output 12C624 ...Repeated for Direct Output 13C627 ...Repeated for Direct Output 14C62A ...Repeated for Direct Output 15C62D ...Repeated for Direct Output 16C630 ...Repeated for Direct Output 17C633 ...Repeated for Direct Output 18C636 ...Repeated for Direct Output 19C639 ...Repeated for Direct Output 20C63C ...Repeated for Direct Output 21C63F ...Repeated for Direct Output 22Table B–10: MODBUS MEMORY MAP (Sheet 55 of 64)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT