GE Multilin G30 Generator Protection System 5-915 SETTINGS 5.2 PRODUCT SETUP5The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.The DIRECT I/O CHANNEL CROSSOVER setting applies to G30s with dual-channel communication cards and allows crossingover messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output networkregardless of the physical media of the two communication channels.The following application examples illustrate the basic concepts for direct input and output configuration. See the Inputsand Outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.Table 5–12: DIRECT INPUT AND OUTPUT DATA RATESMODULE CHANNEL SUPPORTED DATA RATES74 Channel 1 64 kbpsChannel 2 64 kbps7L Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps7M Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps7P Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps7T Channel 1 64 kbps, 128 kbps7W Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps7V Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps2A Channel 1 64 kbps2B Channel 1 64 kbpsChannel 2 64 kbps2G Channel 1 128 kbps2H Channel 1 128 kbps2I Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps2J Channel 1 64 kbps, 128 kbpsChannel 2 64 kbps, 128 kbps76 Channel 1 64 kbps77 Channel 1 64 kbpsChannel 2 64 kbps75 Channel 1 64 kbpsChannel 2 64 kbps7E Channel 1 64 kbpsChannel 2 64 kbps7F Channel 1 64 kbpsChannel 2 64 kbps7G Channel 1 64 kbpsChannel 2 64 kbps7Q Channel 1 64 kbpsChannel 2 64 kbps7R Channel 1 64 kbps7S Channel 1 64 kbpsChannel 2 64 kbpsNOTE