GE Multilin G30 Generator Protection System B-53APPENDIX B B.4 MEMORY MAPPINGBRestricted Ground Fault (Read/Write Grouped Setting) (4 modules)A960 Restricted Ground Fault 1 Function 0 to 1 --- 1 F102 0 (Disabled)A961 Restricted Ground Fault 1 Source 0 to 5 --- 1 F167 0 (SRC 1)A962 Restricted Ground Fault 1 Pickup 0.005 to 30 pu 0.001 F001 80A963 Restricted Ground Fault 1 Slope 0 to 100 % 1 F001 40A964 Restricted Ground Fault 1 Delay 0 to 600 s 0.01 F001 0A965 Restricted Ground Fault 1 Reset Delay 0 to 600 s 0.01 F001 0A966 Restricted Ground Fault 1 Block 0 to 4294967295 --- 1 F300 0A968 Restricted Ground Fault 1 Target 0 to 2 --- 1 F109 0 (Self-reset)A969 Restricted Ground Fault 1 Events 0 to 1 --- 1 F102 0 (Disabled)A96A ...Repeated for Restricted Ground Fault 2A974 ...Repeated for Restricted Ground Fault 3A97E ...Repeated for Restricted Ground Fault 4IEC 61850 Received Analog Settings (Read/Write Setting) (32 modules)AA00 IEC 61850 GOOSE Analog 1 Default Value –1000000 to 1000000 --- 0.001 F060 1000AA02 IEC 61850 GOOSE Analog Input 1 Mode 0 to 1 --- 1 F491 0 (Default Value)AA03 IEC 61850 GOOSE Analog Input 1 Units --- --- --- F207 (none)AA05 IEC 61850 GOOSE Analog Input 1 Per-Unit Base 0 to 999999999.999 --- 0.001 F060 1AA07 ...Repeated for IEC 61850 GOOSE Analog Input 2AA0E ...Repeated for IEC 61850 GOOSE Analog Input 3AA15 ...Repeated for IEC 61850 GOOSE Analog Input 4AA1C ...Repeated for IEC 61850 GOOSE Analog Input 5AA23 ...Repeated for IEC 61850 GOOSE Analog Input 6AA2A ...Repeated for IEC 61850 GOOSE Analog Input 7AA31 ...Repeated for IEC 61850 GOOSE Analog Input 8AA38 ...Repeated for IEC 61850 GOOSE Analog Input 9AA3F ...Repeated for IEC 61850 GOOSE Analog Input 10AA46 ...Repeated for IEC 61850 GOOSE Analog Input 11AA4D ...Repeated for IEC 61850 GOOSE Analog Input 12AA54 ...Repeated for IEC 61850 GOOSE Analog Input 13AA5B ...Repeated for IEC 61850 GOOSE Analog Input 14AA62 ...Repeated for IEC 61850 GOOSE Analog Input 15AA69 ...Repeated for IEC 61850 GOOSE Analog Input 16AA70 ...Repeated for IEC 61850 GOOSE Analog Input 17AA77 ...Repeated for IEC 61850 GOOSE Analog Input 18AA7E ...Repeated for IEC 61850 GOOSE Analog Input 19AA85 ...Repeated for IEC 61850 GOOSE Analog Input 20AA8C ...Repeated for IEC 61850 GOOSE Analog Input 21AA93 ...Repeated for IEC 61850 GOOSE Analog Input 22AA9A ...Repeated for IEC 61850 GOOSE Analog Input 23AAA1 ...Repeated for IEC 61850 GOOSE Analog Input 24AAA8 ...Repeated for IEC 61850 GOOSE Analog Input 25AAAF ...Repeated for IEC 61850 GOOSE Analog Input 26AAB6 ...Repeated for IEC 61850 GOOSE Analog Input 27AABD ...Repeated for IEC 61850 GOOSE Analog Input 28AAC4 ...Repeated for IEC 61850 GOOSE Analog Input 29AACB ...Repeated for IEC 61850 GOOSE Analog Input 30AAD2 ...Repeated for IEC 61850 GOOSE Analog Input 31AAD9 ...Repeated for IEC 61850 GOOSE Analog Input 32IEC 61850 XCBR Configuration (Read/Write Settings and Commands) (6 modules)AB00 Operand for IEC 61850 XCBR1.ST.Loc status 0 to 4294967295 --- 1 F300 0AB02 Command to Clear XCBR1 OpCnt (Operation Counter 0 to 1 --- 1 F126 0 (No)AB03 Operand for IEC 61850 XCBR Check Sync Release 0 to 4294967295 --- 1 F300 0AB05 Operand for IEC 61850 XCBR Open Interlock 0 to 4294967295 --- 1 F300 0Table B–10: MODBUS MEMORY MAP (Sheet 45 of 64)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT