GE Multilin G30 Generator Protection System 2-312 PRODUCT DESCRIPTION 2.4 SPECIFICATIONS22.4.11 TYPE TESTSG30 TYPE TESTS2.4.12 PRODUCTION TESTSTHERMALProducts go through an environmental test based upon anAccepted Quality Level (AQL) sampling process.TEST REFERENCE STANDARD TEST LEVELDielectric voltage withstand EN 60255-5 2.2 kVImpulse voltage withstand EN 60255-5 5 kVDamped oscillatory IEC 61000-4-18 / IEC 60255-22-1 2.5 kV CM, 1 kV DMElectrostatic discharge EN 61000-4-2 / IEC 60255-22-2 Level 3RF immunity EN 61000-4-3 / IEC 60255-22-3 Level 3Fast transient disturbance EN 61000-4-4 / IEC 60255-22-4 Class A and BSurge immunity EN 61000-4-5 / IEC 60255-22-5 Level 3 and 4Conducted RF immunity EN 61000-4-6 / IEC 60255-22-6 Level 3Power frequency immunity EN 61000-4-7 / IEC 60255-22-7 Class A and BVoltage interruption and ripple DC IEC 60255-11 12% ripple, 200 ms interruptsRadiated and conducted emissions CISPR11 / CISPR22 / IEC 60255-25 Class ASinusoidal vibration IEC 60255-21-1 Class 1Shock and bump IEC 60255-21-2 Class 1Seismic IEC 60255-21-3 Class 1Power magnetic immunity IEC 61000-4-8 Level 5Pulse magnetic immunity IEC 61000-4-9 Level 4Damped magnetic immunity IEC 61000-4-10 Level 4Voltage dip and interruption IEC 61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interruptsDamped oscillatory IEC 61000-4-12 2.5 kV CM, 1 kV DMConducted RF immunity, 0 to 150 kHz IEC 61000-4-16 Level 4Voltage ripple IEC 61000-4-17 15% rippleIngress protection IEC 60529 IP20 front, IP10 backCold IEC 60068-2-1 –40°C for 16 hoursHot IEC 60068-2-2 85°C for 16 hoursHumidity IEC 60068-2-30 6 days, variant 1Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHzRF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHzSafety UL 508 e83849 NKCRSafety UL C22.2-14 e83849 NKCR7Safety UL 1053 e83849 NKCRSafety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Overvoltage cat II