7-2 G30 Generator Protection System GE Multilin7.1 COMMANDS 7 COMMANDS AND TARGETS77.1.3 CLEAR RECORDSPATH: COMMANDS CLEAR RECORDSThis menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.7.1.4 SET DATE AND TIMEPATH: COMMANDS SET DATE AND TIMEThe date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The completedate, as a minimum, must be entered to allow execution of this command. The new time and date take effect when theENTER key is pressed.When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time isover-written.The timescale of the entered time is local time, including daylight savings time where and when applicable. COMMANDS CLEAR RECORDSCLEAR USER FAULTREPORTS? NoRange: No, YesCLEAR EVENT RECORDS?NoRange: No, YesCLEAR OSCILLOGRAPHY?NoRange: No, YesCLEAR DATA LOGGER?NoRange: No, YesCLEAR ENERGY?NoRange: No, YesCLEAR UNAUTHORIZEDACCESS? NoRange: No, YesCLEAR DIRECT I/OCOUNTERS? NoRange: No, Yes. Valid only for units with Direct Input/Output module.CLEAR TELEPROTECTCOUNTERS? NoRange: No, YesCLEAR FREQ OOBACCUMULATORS? NoRange: No, YesPRESET FREQ OOBACCUMULATORS? NoRange: No, YesCLEAR ALL RELAYRECORDS? NoRange: No, Yes COMMANDS SET DATE AND TIMESET DATE AND TIME:2000/01/14 13:47:03(YYYY/MM/DD HH:MM:SS)