GE Multilin G30 Generator Protection System 8-18 THEORY OF OPERATION 8.1 DIRECTIONAL PRINCIPLE88 THEORY OF OPERATION 8.1DIRECTIONAL PRINCIPLE 8.1.1 CURRENT DIRECTIONAL PROTECTIONFor better security, the G30 uses the current directional protection principle to dynamically supervise the main current differ-ential function. The directional principle is in effect permanently for low differential currents (region 1 in the Two Regions ofDifferential Characteristic figure) and is switched on dynamically for large differential currents (region 2 in the same figure)by the saturation detector (see the Saturation Detector section) upon detecting CT saturation.The directional principle responds to a relative direction of the fault currents. This means that a reference signal, such astransformer voltage, is not required. The directional principle declares that• if all of the fault currents flow in one direction, the fault is internal, or• if at least one fault current flows in an opposite direction compared with the sum of the remaining currents, the fault isexternal.The directional principle is implemented in two stages.First, based on the magnitude of a given current, it is determined whether the current is a fault current. If so, its relativephase relation has to be considered. The angle check must not be initiated for the load currents as the direction will be outof the transformer even during internal faults. The auxiliary comparator of this stage applies an adaptable threshold. Thethreshold is a fraction of the restraining current. The current from a particular feeder is used for bus directional comparisonif its magnitude is greater than 0.2 × I restraint or it is greater than 2 times its CT rating.Second, for – and only for – the selected fault currents, the phase angle between a given current and the sum of all theremaining currents is checked. The sum of all the remaining currents is the differential current less the current under con-sideration. Therefore, for each, say the pth, current to be considered, the angle between the and phasors is to bechecked.Ideally, during external faults, the said angle is close to 180° (see below); and during internal faults - close to 0 degrees.Figure 8–1: DIRECTIONAL PRINCIPLE OPERATION DURING EXTERNAL FAULTSFigure 8–2: DIRECTIONAL PRINCIPLE OPERATION DURING INTERNAL FAULTSThe G30 implementation calculates the maximum angle for the considered currents and compares it against a fixed thresh-old of 90°. The flag indicating whether the directional protection principle is satisfied is available as the FlexLogic operandXFMR PCNT DIFF DIR A/B/C.I P I D I P–836726A2.CDRBLOCKOPERATEBLOCK⎟⎟⎠⎞⎜⎜⎝⎛− pDpIIIreal⎟⎟⎠⎞⎜⎜⎝⎛− pDpIIIimagIpID - IpExternal Fault ConditionsOPERATE836727A2.CDRBLOCKBLOCK⎟⎟⎠⎞⎜⎜⎝⎛− pDpIIIreal⎟⎟⎠⎞⎜⎜⎝⎛− pDpIIIimagIpID - IpInternal Fault ConditionsOPERATEOPERATE