8.1 Self-diagnostic Function8-38.1.2 Operation Mode When an Error Occurs• Normally, when an error occurs, the operation stops.• For some errors, the user may select whether operation is to be continued or stopped bysetting the system registers. "PLC Configuration" dialog box of FPWIN GR7To specify the steps to be taken by the FPWIN GR7 if a PLC error occurs, select "Systemregister settings" under "Option" on the menu bar, and click on the "Action on Error" tab. Thescreen shown below is displayed.KEY POINTS• When the checkbox of the system register no. 25 "Stop operation whenpositioning operation error occurs" is unchecked, only the operation of theaxis in which the positioning error occurs stops and the operations of otheraxes continue.