FP Mode11-211.1 FPΣ Mode11.1.1 Overview of FPΣ Mode• FPΣ mode is a mode for using projects for the conventional model FPΣ series in FP0H.Although some functions of FP0H are limited, compatibility with FPΣ is maintained. Comparison of specificationsItemSpecificationsConventionalmodelFPΣ seriesFP0H seriesFPΣ modeFP0H modeValues in [ ] are forC32E only.Program capacity (Note 1) 32K steps 24K / 32K steps 24K / 32K / [40K / 64K]stepsData register capacity(Note1) 32765 words 65533 / 32765 words 65533 / 32765 / [24573 /12285] wordsAutomaticbackup incase ofpower outage(Note 2)InternalrelayR2480 to R255F(Fixed)R2480 to R255F(Fixed)R5040 to R511F[R2480 to R255F]DataregisterDT32710 to DT32764(Fixed)DT32710 to DT32764(Fixed)[DT11970 to DT12284DT24258 to DT24572]DT32450 to DT32764DT65218 to DT65532(Note 2)Pulse/PWM output setting(System register no. 402) No setting Cannot be set. Can be set.Positioning control mode(System register no. 407) Cannot be set.FPΣcompatibleinstruction mode(Fixed)Select Table setting modeor FPΣ compatibleinstruction mode.Values whensystemregisters areinitializedNo.7 248 (Fixed) 248 (Fixed)[C32]Initialize according tosystem register no. 1.[C32E]504 (Fixed)No.8 32710 (Fixed) 32710 (Fixed) Initialize according tosystem register no. 0.No.407 Cannot be set. FPΣ compatibleinstruction mode Table setting modeNo.430 toNo.433 Cannot be set. No setting 1 ms(Note 1): Program capacities and data register capacities can be changed by the setting of the system register no. 0.(Note 2): In the FP0H mode, the automatic backup areas for internal relays and data registers vary according to thesettings of system register nos. 0 and 1.