10.5 Interrupt Program Activation10-2910.5.2 Interrupt Activation When F165 (CAM0) is ExecutedFor the cam control instruction F165 (CAM0), the start condition varies according to themagnitude of the ON set value and OFF set value. Also, the interrupt program is activatedwith each target value of up to 32 points. Activation of interrupt programON set value < OFF setvalueON set value > OFF setvalueON set value = OFF setvalueWhenaddedWhensubtractedDescriptionWhen the elapsed value islarger than or equal to the ONset value and smaller than theOFF set value, the interruptprogram is activated.When the elapsed value issmaller than the ON set valueand larger than or equal to theOFF set value, the interruptprogram is activated.When the elapsed valuereaches the ON set value (=OFF set value), the interruptprogram is activated.