UniPOS IFS7002 two signal loopsInstruction Manual Page 12Revision 11/01.17 Of 145Conditions of the fire control panel IndicationFault condition -All faults except for Battery LowCommon indicator Fault condition– continuous yellow lightFault condition – System error Indicator System error - continuousyellow lightFault condition -Fault in mains supplyIndicator Fault in mains supply -continuous yellow lightDisabled component -Disabled zone, addressable device or monitoredoutputIndicator Disabled component -continuous yellow lightTest condition Indicator Test –continuous yellow lightFire condition Local sounder – discontinuous signal: 0.5 ssound, followed by 0.5s breakFault condition - All faults except for Battery Low Local sounder – discontinuous signal: 1 ssound, followed by 1 s breakFault condition -Low batteryLocal sounder – discontinuous signal: 1 ssound, followed by 3 s break6.3. Zone in Coincidence ModeCoincidence Mode allows for enhanced certainty that a zone has entered Fire condition, phaseFire condition stage I. The mode requires that at least two fire detectors from this zone shall beactivated to trigger Fire condition, phase Fire condition stage I in the fire control panel.The Coincidence Mode is not applicable to manual call points. If a manual call point, included in azone set to Coincidence Mode, responds, the fire control panel enters Fire condition, phase Firecondition stage II in this particular zone.Upon activation of an automatic fire detector from a zone set to Coincidence Mode, but the firecontrol panel has not entered Fire condition in this zone, then: If no other automatic fire detector is activated, the zone enters Pre-Fire condition; If another automatic fire detector is activated, i.e. the zone is in Pre-Fire condition, then thefire control panel enters Fire condition, phase Fire condition stage I, in this particular zone.Exit from Pre-Fire condition in a zone is done: Upon activation of a second automatic fire detector in the zone (the fire control panel entersFire condition, phase Fire condition stage I, in this particular zone); Upon activation of a manual call point in the zone from the Pre-Fire condition (the fire controlpanel enters Fire condition, phase Fire condition stage II, in this particular zone); On manual operation from the button “Reset Fire” (password for Access Level 2 is required) –the control panel will send command “Reset to duty mode” to the automatic detector in firecondition.To set a zone in Coincidence Mode you need to appoint the parameter Coincidence Mode for thiszone (see section 13.5.3).While using the Coincidence Mode in a zone, we recommend you to include just one group ofautomatic fire detectors (minimum 2 fire detectors) in this zone, allocated in one and the same room,so upon activation of any two fire detectors you obtain a firm indication for fire in the room.Table 2Means of control Condition of the firecontrol panelAccesslevel OperationButton Reset Fire Fire condition Level 2 To exit the Fire condition