UniPOS IFS7002 two signal loopsInstruction Manual Page 41Revision 11/01.17 Of 14512.2.9.3. Screen Zone ParametersThe screen displays common zoneparameters: Manual call point priority –where the manual call pointshave priority, their response willforce the zone to enter FireCondition Phase 2; where themanual call points do not havepriority, their response willforce the zone to enter FireCondition Phase 1, or, in otherwords, the manual call pointwill be treated as automatic firedetectors; Coincidence Mode – whenoperating in CoincidenceMode,the zone will enter Fire Condition Phase 1 upon activation of at least two low priority firedetectors; Time Fire Phase 1 – Phase 2 – this is the time delay before the fire control panel proceedsfrom Fire Condition Stage I to Fire Condition Stage II in this particular zone ; Inspection time – time added to the remaining time, by pressing button , before the zoneproceeds from Fire Condition Stage I to Fire Condition Stage II.12.2.10. Menu Device StatusThe menu provides information for the current status of the devices. Enter the menu to display: A screen with the message No integrated devices, where no devices are present; the onlyoption is to exit the menu; A screen for the status of thefirst device, where somedevices are present:Buttons and seen onthe right panel section appear whenmore than one device is available;the Go to field and the digit buttonsappear when more than two devicesare available.Buttons and allow theuser to switch between the next andthe previous device (if available).When you press a digit button,the button appears and the Goto field is activated; then you mayenter a random 3-digit number for thedevice. To edit the number press button , and the last entered digit is deleted.The devices get numbers according to the following sequence: from the first device in Loop 1 tothe last device in Loop 2; from the first device in Loop 2 to the last device in Loop 2.When you press button it displays a screen for the status of the device, which number is inthe field: If you enter 0, the first device will be selected;Mode:DAY LOC АctInp 0000 12:54:57 Sat 13 Mar 2010FIRE CONTROL PANEL IFS7002UniPOSParameters: Zone 1Manual call point Priority: YesCoincidence Mode: NoTime Fire Phase 1 – Phase 2: 120 sInspection time: 120 sMode:DAY LOC АctInp 0000 14:22:00 Sat 13 Mar 2010FIRE CONTROL PANEL IFS7002UniPOSList of values Devices Total: 8 Go to:Loop01 Аddr001 Zone001Point 1.001Device type: FD7110Temperature +022 С Class: A2SStatus: Isolator Off LED Off0 1 2 3 4 5 6 7 8 9 СС